How to Winterize Your Sprinkler System (Drain, Blow-Out & Backflow Protection)
How to Winterize Your Sprinkler System
Freezing temps can crack backflows, valves, and underground lines in a single night—water expands about 9% when it freezes—leading to leaks, costly repairs, and spring headaches. Winterizing your sprinkler system protects the backflow (and your water supply), prevents split pipes and flooded valve boxes, extends equipment life, and makes spring start-up fast and stress-free. Whether you choose a simple gravity drain or a controlled air blow-out, shutting off the supply, draining lines, and covering the backflow are quick steps that save money and help you stay code- and insurance-friendly all winter.
The good news: with a quick shut-down and either a manual drain or controlled blow-out, you can protect your system in under an hour.
Before You Start
- Pick your method: Manual drain (gravity) or controlled air blow-out.
- Know your backflow: PVB/RP/DC assemblies need to be drained and protected—never push high pressure air through the backflow.
- Controller: Put your timer on “Rain/Standby” or OFF so the system stays shut down after winterizing.
- Safety: Wear eye protection; if you’re unsure about air pressure or gas/power connections to pumps, hire a pro.
Step 1 — Shut Off & Isolate
- Close the irrigation main shutoff feeding the system (usually near the backflow or inside the house).
- If you have a backflow/vacuum breaker, turn the two shutoff handles to OFF, then open the test cocks ¼–½ turn to vent.
- Open at least one zone valve or manual drain to relieve pressure.
Step 2 — Drain Method (No Compressor)
- Open all manual drain valves at low points and end-caps on lateral lines; let them trickle until empty.
- At the backflow, leave test cocks angled downward to finish draining; set both shutoff handles at ~45° so trapped water can expand.
- Cap/close drains once empty; leave the controller OFF.
Step 3 — Controlled Blow-Out Method
- Attach a blow-out adapter at the manifold or a threaded port downstream of the backflow.
- Hook up a compressor with a pressure regulator. Start at ~40 PSI; increase slightly if needed.
- Run one zone at a time from the controller. Let it blow until only a fine mist appears (usually 1–3 minutes per zone). Don’t run solenoids dry for long; cycle through zones.
- When finished, close the adapter, vent any residual air, and disconnect the compressor.
Step 4 — Protect the Backflow/Vacuum Breaker
- Confirm the backflow body and bonnets are fully drained (use the test cocks).
- Slip on an insulated cover and seal drafts from below. In very cold/windy areas, consider a listed enclosure or heat-tape solution per instructions.
Quick Reference Table
| Task | What to Do | What to Avoid |
|---|---|---|
| Shutoff | Close main feeding irrigation; set controller OFF | Leaving controller active |
| Backflow | Drain via test cocks; handles at ~45° | Forcing high-pressure air through backflow |
| Blow-Out | 40–50 PSI, one zone at a time | Exceeding ratings; continuous run on dry valves |
| Finish | Install insulated cover; verify no leaks | Leaving drains closed with water trapped |
Shop our Favorites
Insulated Backflow Covers
Sprinkler Blow-Out Adapters
Spring Start-Up (Save This)
- Close all test cocks/drains; open isolation valves slowly.
- Pressurize one zone at a time; check for leaks at valves and the backflow bonnet/poppet.
- Flush lines briefly with heads removed if you see debris; then reinstall and set your seasonal watering schedule.
Code note: Always follow local plumbing codes and manufacturer instructions. If you’re on a shared/commercial system, a certified backflow tester may be required.
Winterization FAQs
Do I need to blow out the system, or can I just drain it?
If your system has manual low-point drains and short, simple runs, gravity draining can work. For mixed elevations or long laterals, a controlled air blow-out is more reliable. Never exceed component pressure ratings.
What air pressure should I use for a blow-out?
Start around 40–50 PSI for most spray/rotor zones and run one zone at a time until only a fine mist remains. Dial down for drip (≈15–25 PSI) or drain drip manually to avoid damage.
Can I push compressed air through the backflow/vacuum breaker?
No. Connect the compressor downstream of the backflow and keep the backflow drained with the test cocks open. Use a proper sprinkler blow-out adapter.
When should I winterize?
Before recurring overnight lows around 32°F (0°C). If a sudden cold snap is forecast, at least drain the backflow immediately and cover it the same day.
How do I protect the backflow from freezing?
Drain via test cocks, set the shutoff handles at ~45°, and install an insulated backflow cover. In very cold/windy areas, consider a listed enclosure or heat-tape (per instructions).
Read our Article : Freeze Protecting Your Pressure Vacuum Breaker
What should I do with the controller after winterizing?
Set it to Rain/Standby or OFF so the system stays shut down. If your controller has a winterize mode, use it.
Should I hire a pro?
Hire a licensed pro if you’re unsure about safe air pressure, electrical/pump isolation, or code compliance. Many municipalities require certified backflow testing annually.
Blog posts
-
Choosing a Rinnai Tankless Water Heater: Sizing, Cost, Maintenance & Most-Asked Questions
Leer ahoraThinking Rinnai tankless? This guide answers the most common questions—how to size, how often to flush, typical issues, condensing vs. non-condensing, indoor vs. outdoor, warranties, and more—so you can pick the right model with confidence.
-
Snow-Melt Systems for Walkways, Paths & Driveways (How They Work, Cost, Install & FAQs)
Leer ahoraSnow-melt heating uses embedded electric mats or cables to automatically clear ice and snow from walkways, paths, and driveways—no salt, no scraping. Here’s how it works, when to use it, what it costs, and what to buy.
-
What Is Point-of-Use Reverse Osmosis (RO)? Benefits, Use Cases & FAQs
Leer ahoraPoint-of-use reverse osmosis (under-sink RO) delivers crisp, great-tasting water at the faucet by reducing TDS and chlorine taste/odor—ideal for cooking, coffee, baby formula, and ice—with optional remineralization for those who want minerals/electrolytes back for taste.

Dejar un comentario